J.H. Larson Company | |
![]() |
||
| Acme Buck-Boost Transformer Selection
Chart 120x240 Volts Primary–12/24 Volts Secondary |
||
| Three Phase | BOOSTING | BUCKING | |||||||||||
| Line Voltage (Available) | 189Y 109 |
196Y 113 |
201Y 116 |
208Y 120 |
189 | 208 | 220 | 229 | 230 | 250 | 255 | 265 | |
| Load Voltage (Output) | 208 | 234 | 240 | 230 | 208 | 230 | 242 | 208 | 208 | 227 | 232 | 240 | |
| Quanity Required | 3 | 3 | 3 | 3 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |
| Catalog Number | Connection Diagram |
A–A | F–F | F–F | A–A | B–B | B–B | B–B | C–C | E–E | E–E | E–E | E–E |
| T-1-81047 0.05 KVA |
KVA Amps Fuse/Breaker |
1.50 4.17 10 |
0.84 2.08 6 |
0.87 2.08 6 |
1.66 4.17 10 |
0.75 2.08 6 |
0.83 2.08 6 |
0.87 2.08 6 |
1.58 4.39 10 |
0.83 2.30 6 |
0.90 2.29 6 |
0.92 2.29 6 |
0.95 2.29 6 |
| T-1-81048 0.10 KVA |
KVA Amps Fuse/Breaker |
3.00 8.33 15 |
1.69 4.17 10 |
1.73 4.17 10 |
3.32 8.33 15 |
1.50 4.17 10 |
1.66 4.17 10 |
1.75 4.17 10 |
3.16 8.77 15 |
1.66 4.61 10 |
1.80 4.59 10 |
1.84 4.58 10 |
1.91 4.58 10 |
| T-1-81049 0.15 KVA |
KVA Amps Fuse/Breaker |
4.50 12.50 20 |
2.53 6.25 15 |
2.60 6.25 15 |
4.98 6.25 20 |
2.25 6.25 15 |
2.49 6.25 15 |
2.62 6.25 15 |
4.74 13.16 20 |
2.49 6.91 15 |
2.71 6.88 15 |
2.76 6.87 15 |
2.86 6.88 15 |
| T-1-81050 0.25 KVA |
KVA Amps Fuse/Breaker |
7.51 20.83 30 |
4.22 10.42 20 |
4.33 10.42 20 |
8.30 20.83 30 |
3.75 10.42 15 |
4.15 10.42 15 |
4.37 10.42 15 |
7.90 21.94 30 |
4.15 11.52 15 |
4.51 11.47 15 |
4.60 11.45 15 |
4.76 11.46 15 |
| T-1-81051 0.50 KVA |
KVA Amps Fuse/Breaker |
15.01 41.67 60 |
8.44 20.83 35 |
8.66 20.83 35 |
16.60 41.67 60 |
7.51 20.83 30 |
8.30 20.83 30 |
8.73 20.83 30 |
15.80 43.87 60 |
8.30 23.04 30 |
9.02 22.94 30 |
9.20 22.90 30 |
9.53 22.92 30 |
| T-1-81052 0.75 KVA |
KVA Amps Fuse/Breaker |
22.52 62.50 90 |
12.67 31.25 50 |
12.99 31.25 50 |
24.90 62.50 90 |
11.26 31.25 45 |
12.45 31.25 45 |
13.10 31.25 45 |
23.71 65.81 80 |
12.45 34.56 40 |
13.53 34.42 40 |
13.80 34.45 4 |
14.29 34.38 40 |
| T-1-11683 1.00 KVA |
KVA Amps Fuse/Breaker |
30.02 83.31 125 |
16.89 41.67 70 |
17.32 41.67 70 |
33.20 83.31 125 |
15.01 41.67 60 |
16.60 41.67 60 |
17.46 41.67 60 |
31.61 87.74 110 |
16.60 46.07 60 |
18.04 45.89 60 |
18.40 45.80 60 |
19.05 45.83 60 |
| T-1-11684 1.50 KVA |
KVA Amps Fuse/Breaker |
45.03 125.00 175 |
25.33 62.50 100 |
25.98 62.50 100 |
49.80 125.00 175 |
22.52 62.50 90 |
24.90 62.50 90 |
26.20 62.50 90 |
47.41 131.61 175 |
24.90 69.11 80 |
27.06 68.83 80 |
27.60 68.70 80 |
28.58 68.75 80 |
| T-1-11685 2.00 KVA |
KVA Amps Fuse/Breaker |
60.04 166.67 250 |
33.77 83.33 125 |
34.64 83.33 125 |
66.40 167.67 250 |
30.02 83.33 125 |
33.20 83.33 125 |
34.93 83.33 125 |
63.22 175.48 225 |
33.20 92.15 110 |
36.08 91.78 110 |
36.81 91.59 110 |
38.11 91.67 110 |
| T-1-11686 3.00 KVA |
KVA Amps Fuse/Breaker |
90.07 250.00 350 |
50.66 125.00 200 |
51.96 125.00 200 |
99.59 250.00 350 |
45.03 125.00 175 |
49.80 125.00 175 |
52.39 125.00 175 |
94.83 263.22 350 |
49.80 138.22 175 |
54.13 137.67 175 |
55.21 137.39 175 |
57.16 137.50 175 |
| T-1-11687 5.00 KVA |
KVA Amps Fuse/Breaker |
150.11 416.67 600 |
84.44 208.33 350 |
86.60 208.33 350 |
165.99 416.67 600 |
75.06 208.33 300 |
82.99 208.33 300 |
87.32 208.33 300 |
158.05 438.70 600 |
82.99 230.37 300 |
90.21 229.44 300 |
92.02 228.99 300 |
95.26 229.17 300 |
| T-1-11688[1] 7.50 KVA |
KVA Amps Fuse/Breaker |
225.17 625.00 1000 |
126.66 312.50 500 |
129.90 312.50 500 |
248.98 625.00 1000 |
112.58 312.50 450 |
124.49 312.50 450 |
130.99 312.50 450 |
237.07 658.05 800 |
124.49 345.55 400 |
135.32 344.16 400 |
138.02 343.48 400 |
142.89 343.75 400 |
| T-1-11689[1] 10.00 KVA |
KVA Amps Fuse/Breaker |
300.22 833.33 1200 |
168.87 416.67 700 |
173.21 416.67 700 |
331.98 833.33 1200 |
150.11 416.67 600 |
165.99 416.67 600 |
174.65 416.67 600 |
316.10 877.40 1200 |
165.99 460.74 600 |
180.42 458.88 600 |
184.03 457.97 600 |
190.53 458.33 600 |
| Quanity Required | 3 | 3 | 3 | 3 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |
| Catalog Number | Connection Diagram |
A–A | F–F | F–F | A–A | B–B | B–B | B–B | C–C | E–E | E–E | E–E | E–E |
| Note: | Inputs and outputs may be reversed; KVA remains constant. All applications in black are suitable for 50/60 Hz. All applications in red are suitable for 60 Hz. only. |
| [1] | It is necessary to utilize multiple conductors on the secondary (X1, X2, X3, and X4) terminals of these transformers. |