J.H. Larson Company  
FPE Logo
FPE Buck-Boost Transformer Selection Chart
240x480 Volts Primary–24/48 Volts Secondary
 Single Phase BOOSTING BUCKING
Line Voltage (Available)  230 380 416 425 430 435 440 450 465 132 277 480 480 504
Load Voltage (Output)  276 418 458 468 473 457 462 495 483 126 231 436 457 480
Catalog Number Connection
Diagram
B D D D D C C D C C B D C C
SB24N.050F
0.05 KVA
KVA
Amps
Fuse**
0.29
1.04
2*
0.44
1.04
1.5*
0.48
1.04
1.5*
0.49
1.04
1.5*
0.49
1.04
1.5*
0.95
2.08
3
0.96
2.08
3
0.52
1.04
1.5*
1.01
2.08
3
0.28
2.19
3
0.29
1.25
1.5*
0.50
1.15
1.5*
1.02
2.19
3
1.05
2.19
3
SB24N.100F
0.10 KVA
KVA
Amps
Fuse**
0.58
2.08
4*
0.87
2.08
3
0.95
2.08
3
0.97
2.08
3
0.99
2.08
3
1.90
4.17
6
1.93
4.17
6
1.03
2.08
3
2.01
4.17
6
0.55
4.38
6
0.58
2.50
3
1.00
2.29
3
2.00
4.38
6
2.10
4.38
6
SB24N.150F
0.15 KVA
KVA
Amps
Fuse**
0.86
3.13
6
1.31
3.13
5*
1.43
3.13
5*
1.46
3.13
5*
1.48
3.13
5*
2.85
6.25
10
2.89
6.25
10
1.55
3.13
5*
3.02
6.25
10
0.83
6.56
10
0.87
3.75
5*
1.50
3.44
5*
3.00
6.56
10
3.15
6.56
10
SB24N.250F
0.25 KVA
KVA
Amps
Fuse**
1.44
5.21
10
2.18
5.21
8*
2.38
5.21
8*
2.43
5.21
8*
2.46
5.21
8*
4.76
10.42
15
4.81
10.42
15
2.58
5.21
8*
5.03
10.42
15
1.38
10.94
15
1.44
6.25
8*
2.50
5.73
8*
5.00
10.94
15
5.25
10.94
15
SB24N.500F
0.50 KVA
KVA
Amps
Fuse**
2.88
10.42
20
4.35
10.42
15
4.77
10.42
15
4.87
10.42
15
4.93
10.42
15
9.52
20.83
30
9.63
20.83
30
5.16
10.42
15
10.06
20.83
30
2.75
21.88
30
2.89
12.50
15
5.00
11.46
15
10.00
21.88
30
10.50
21.88
30
SB24N.750F
0.75 KVA
KVA
Amps
Fuse**
4.31
15.63
25
6.53
15.63
25
7.15
15.62
25
7.30
15.63
25
7.39
15.63
25
14.27
31.25
45
14.44
31.25
45
7.73
15.63
25
15.09
31.25
45
4.13
32.81
40
4.33
18.75
20
7.50
17.91
20
15.00
32.81
40
15.75
17.19
40
SB24N1F
1.00 KVA
KVA
Amps
Fuse**
5.75
20.83
35
8.71
20.83
30
9.53
20.83
30
9.74
20.83
30
9.85
20.83
30
19.03
41.67
60
19.25
41.67
60
10.31
20.83
30
20.13
41.67
60
5.50
43.75
60
5.77
25.00
30
10.00
22.92
30
20.00
43.75
60
21.00
43.75
60
SB24N1.5F
1.50 KVA
KVA
Amps
Fuse**
8.63
31.25
50
13.06
31.25
45
14.30
31.25
45
14.61
31.25
45
14.78
31.25
45
28.55
62.50
90
28.88
62.50
90
15.47
31.25
45
30.19
62.50
90
8.25
65.63
80
8.66
37.50
40
15.00
34.37
40
30.00
65.63
80
31.50
65.63
80
SB24N2F
2.00 KVA
KVA
Amps
Fuse**
11.50
41.67
70
17.42
41.67
60
19.07
41.67
60
19.48
41.67
60
19.71
41.67
60
38.06
83.33
110
38.50
83.33
110
20.63
41.67
60
40.25
83.33
110
11.00
87.50
110
11.54
50.00
60
20.00
45.83
60
40.00
87.50
110
42.00
87.50
110
SB24N3F
3.00 KVA
KVA
Amps
Fuse**
17.25
62.50
100
26.13
62.50
90
28.60
62.50
90
29.22
62.50
90
29.56
62.50
90
57.09
125.00
175
57.75
125.00
175
30.94
62.50
90
60.38
125.00
175
16.50
131.25
175
17.31
75.00
80
30.00
68.75
80
60.00
131.25
175
63.00
131.25
175
SB24N5F
5.00 KVA
KVA
Amps
Fuse**
28.75
104.17
175
43.54
104.17
150
47.67
104.17
150
48.70
104.17
150
49.27
104.17
150
95.16
208.33
300
96.25
208.33
300
51.56
104.17
150
100.63
208.33
300
27.50
218.75
300
28.85
125.00
150
50.00
114.58
150
100.00
218.75
300
105.00
218.75
300
Catalog Number Connection
Diagram
B D D D D C C D C C B D C C
 * Non-NEC standard fuse size (NEC 240-6), check with local authorities for use of next larger size.
 ** Maximum fuse or circuit breaker size per NEC 450-4.
 
  Output for lower voltage can be found by:  Rated Output Voltage
Rated Input Voltage
x  Input Actual Voltage = Output New Voltage.
 
Output KVA available at reduced voltage can be found by:  Actual Input Voltage
Rated Input Voltage
x  Output KVA = New KVA Rating.
 

 Other Selection Charts
 120x240V - 12/24V 1Ø Phase
 120x240V - 12/24V 3Ø Phase
 120x240V - 16/32V 1Ø Phase
 120x240V - 16/32V 3Ø Phase
 240x480V - 24/48V 3Ø Phase
  Back to Industry Tables Back to JHL Home page Disclaimer