J.H. Larson Company | |
![]() |
||
| FPE Buck-Boost Transformer Selection
Chart 240x480 Volts Primary–24/48 Volts Secondary |
||
| Three Phase | BOOSTING | BUCKING | |||||||||||||||
| Line Voltage (Available) | 399Y 230 |
380 | 430 | 440 | 460 | 460 | 480 | 480 | 440 | 440 | 460 | 460 | 460 | 480 | 500 | 500 | |
| Load Voltage (Available) | 480Y 277 |
418 | 473 | 462 | 506 | 483 | 528 | 504 | 400 | 419 | 438 | 418 | 457 | 436 | 455 | 476 | |
| Catalog Number | Connection Diagram |
E | G | G | H | G | H | G | H | G | H | H | G | H | G | G | H |
| SB24N.050F 0.05 KVA |
KVA Amps Fuse** |
0.86 1.04 2* |
0.75 1.04 1.5* |
0.85 1.04 1.5* |
1.67 2.08 3 |
0.91 1.04 1.5* |
1.74 2.08 3 |
0.95 1.04 1.5* |
1.82 2.08 3 |
0.79 1.15 1.5* |
1.59 2.19 3 |
1.66 2.19 3 |
0.83 1.15 1.5* |
1.73 2.19 3 |
0.87 1.15 1.5* |
0.90 1.15 1.5* |
1.80 2.19 3 |
| SB24N.100F 0.10 KVA |
KVA Amps Fuse** |
1.73 2.08 4* |
1.51 2.08 3 |
1.71 2.08 3 |
3.33 4.17 6 |
1.83 2.08 3 |
3.49 4.17 6 |
1.91 2.08 3 |
3.64 4.17 6 |
1.59 2.29 3 |
3.18 4.38 6 |
3.32 4.38 6 |
1.66 2.29 3 |
3.46 4.38 6 |
1.73 2.29 3 |
1.80 2.29 3 |
3.61 4.38 6 |
| SB24N.150F 0.15 KVA |
KVA Amps Fuse** |
2.59 3.13 6 |
2.26 3.13 5* |
2.56 3.13 5* |
5.00 6.25 10 |
2.74 3.13 5* |
5.23 6.25 10 |
2.86 3.13 5* |
5.46 6.25 10 |
2.38 3.44 5* |
4.76 6.56 10 |
4.98 6.56 10 |
2.49 3.44 5* |
5.20 6.56 10 |
2.60 3.44 5* |
2.71 3.44 5* |
5.41 6.56 10 |
| SB24N.250F 0.25 KVA |
KVA Amps Fuse** |
4.32 5.21 10 |
3.77 5.21 8* |
4.27 5.21 8* |
8.34 10.42 15 |
4.56 5.21 8* |
8.71 10.42 15 |
4.76 5.21 8* |
9.09 10.42 15 |
3.97 5.73 8* |
7.94 10.94 15 |
8.30 10.94 15 |
4.15 5.73 8* |
8.66 10.94 15 |
4.33 5.73 8* |
4.51 5.73 8* |
9.02 10.94 15 |
| SB24N.500F 0.50 KVA |
KVA Amps Fuse** |
8.64 10.42 20 |
7.54 10.42 15 |
8.53 10.42 15 |
16.67 20.83 30 |
9.13 10.42 15 |
17.43 20.83 30 |
9.53 10.42 15 |
18.19 20.83 30 |
7.94 11.46 15 |
15.88 21.88 30 |
16.60 21.88 15 |
8.30 11.46 15 |
17.32 21.88 30 |
8.66 11.46 15 |
9.02 11.46 15 |
18.04 21.88 30 |
| SB24N.750F 0.75 KVA |
KVA Amps Fuse** |
12.96 15.62 25 |
11.31 15.63 25 |
12.80 15.63 25 |
25.01 31.25 45 |
13.69 15.63 25 |
26.14 31.25 45 |
14.29 15.63 25 |
27.28 31.25 45 |
11.91 17.19 20 |
23.82 32.81 40 |
24.90 32.81 40 |
12.45 17.19 20 |
25.98 32.81 40 |
12.99 17.19 20 |
13.53 17.19 20 |
27.06 32.81 40 |
| SB24N1F 1.00 KVA |
KVA Amps Fuse** |
17.28 20.83 35 |
15.08 20.83 30 |
17.07 20.83 30 |
33.34 41.67 60 |
18.26 20.83 30 |
34.86 41.67 60 |
19.05 20.83 30 |
36.37 41.67 60 |
15.88 22.92 30 |
31.75 43.75 60 |
33.20 43.75 60 |
16.60 22.92 30 |
34.64 43.75 60 |
17.32 22.92 30 |
18.04 22.92 30 |
36.08 43.75 60 |
| SB24N1.5F 1.50 KVA |
KVA Amps Fuse** |
25.92 31.25 50 |
22.62 31.25 45 |
25.60 31.25 45 |
50.01 62.50 90 |
27.39 31.25 45 |
52.29 62.50 90 |
28.58 31.25 45 |
54.66 62.50 90 |
23.82 34.38 40 |
47.63 65.63 80 |
49.80 65.63 80 |
24.90 34.38 40 |
51.96 65.63 80 |
25.98 34.37 40 |
27.06 34.37 40 |
54.13 65.63 80 |
| SB24N2F 2.00 KVA |
KVA Amps Fuse** |
34.55 41.67 70 |
30.17 41.67 60 |
34.14 41.67 60 |
66.68 83.33 70 |
36.52 41.67 60 |
69.72 83.33 70 |
38.11 41.67 60 |
72.75 83.33 70 |
31.75 45.83 60 |
63.51 87.50 70 |
66.40 87.50 70 |
33.20 45.83 60 |
69.28 87.50 70 |
34.64 45.83 60 |
36.08 45.83 60 |
72.17 87.50 70 |
| SB24N3F 3.00 KVA |
KVA Amps Fuse** |
51.83 62.50 100 |
45.25 62.50 90 |
51.20 62.50 90 |
100.03 125.00 175 |
54.78 62.50 90 |
104.57 125.00 175 |
57.16 62.50 90 |
109.12 125.00 175 |
47.63 68.75 80 |
95.26 131.25 175 |
99.59 131.25 175 |
49.80 68.75 80 |
103.92 131.25 175 |
51.96 68.75 80 |
54.13 68.75 80 |
108.25 131.25 175 |
| SB24N5F 5.00 KVA |
KVA Amps Fuse** |
86.39 104.17 175 |
75.42 104.17 150 |
85.34 104.17 150 |
166.71 208.33 300 |
91.29 104.17 150 |
174.29 208.33 300 |
95.26 104.17 150 |
181.87 208.33 300 |
79.39 114.58 150 |
158.77 218.75 300 |
165.99 218.75 300 |
82.99 114.58 150 |
173.21 218.75 300 |
86.60 114.58 150 |
90.21 114.58 150 |
180.42 218.75 300 |
| No. of Transformers | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |
| Catalog Number | Connection Diagram |
E | G | G | H | G | H | G | H | G | H | H | G | H | G | G | H |
| * Non-NEC standard fuse size (NEC 240-6), check with local authorities for use of next larger size. | |||
| ** Maximum fuse or circuit breaker size per NEC 450-4. |
|||
| Output for lower voltage can be found by: | Rated Output Voltage Rated Input Voltage |
x Input Actual Voltage = Output New Voltage. | |
| Output KVA available at reduced voltage can be found by: | Actual Input Voltage Rated Input Voltage |
x Output KVA = New KVA Rating. | |