Thermolec Electric Plenum Heater Selection Guide

US Models KW @ 240V Heating Sequences Current (Amps)
Mono-Energy Dual-Energy Plenum Heater Breaker
T-5 U T-5 U-DFC 5 1 20.8 30
T-10 U T-10 U-DFC 10 2 41.6 60
T-15 U T-15 U-DFC 15 3 62.5 2 X 40
T-20 U T-20 U-DFC 20 4 83.3 2 X 60
T-25 U T-25 U-DFC* 25 4 104.0 3 X 50
T-30 U T-30 U-DFC 30 4 124.0 3 X 60
* Larger frame size required for models 25/30 kw