| Table 310-16. (1999 N.E.C.) Allowable Ampacities of Insulated Conductors Rated 0 through 2000 Volts 60° to 90°C (140° to 194°F) Not More Than Three Current-Carrying Conductors in Raceway or Cable or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F) |
| SIZE | Temperature Rating of Conductor. See Table 310-13. | |||||
| 60°C (140°F) |
75°C (167°F) |
90°C (194°F) |
60°C (140°F) |
75°C (167°F) |
90°C (194°F) |
|
| AWG kcmil |
TYPES TW* UF* |
TYPES FEPW* RH*, RHW* THHW* THW* THWN* XHHW* USE*, ZW* |
TYPES TBS, SA SIS, FEP* FEPB*, MI RHH*, RHW-2 THHN* THHW* THW-2* THNW-2* USE-2*, XHH XHHW* XHHW-2* ZW-2 |
TYPES TW* UF* |
TYPES FEPW* RH*, RHW* THHW* THW* THWN* XHHW* USE*, ZW* |
TYPES TBS, SA SIS, FEP* FEPB*, MI RHH*, RHW-2 THHN* THHW* THW-2* THNW-2* USE-2*, XHH XHHW* XHHW-2* ZW-2 |
| COPPER | ALUMINUM OR COPPER-CLAD ALUMINUM | |||||
| 18 | - - - - | - - - - | 14 | - - - - | - - - - | - - - - |
| 16 | - - - - | - - - - | 18 | - - - - | - - - - | - - - - |
| 14 | 20* | 20* | 25* | - - - - | - - - - | - - - - |
| 12 | 25* | 25* | 30* | 20* | 20* | 25* |
| 10 | 30 | 35* | 40* | 25 | 30* | 35* |
| 8 | 40 | 50 | 55 | 30 | 40 | 45 |
| 6 | 55 | 65 | 75 | 40 | 50 | 60 |
| 4 | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 | 85 | 100 | 110 | 65 | 75 | 85 |
| 2 | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 | 110 | 130 | 150 | 85 | 100 | 115 |
| 1/0 | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 | 195 | 230 | 260 | 150 | 180 | 205 |
| 250 | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 | 240 | 285 | 320 | 190 | 230 | 255 |
| 350 | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 | 320 | 380 | 430 | 260 | 310 | 350 |
| 600 | 355 | 420 | 475 | 280 | 340 | 385 |
| 700 | 385 | 460 | 520 | 310 | 375 | 420 |
| 750 | 400 | 475 | 535 | 320 | 385 | 435 |
| * Unless otherwise specifically permitted elsewhere in the National Electrical Code Book, the overcurrent protection for conductor types marked with an asterisk shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No. 12, 25 amperes for No. 10 aluminum & copper-clad aluminum after any correction factors for ambient temperature and number of conductors has been applied. |