Table 250.66 Grounding Electrode Conductor
for Alternating-Current System
Size of Largest Ungrounded
Service-Entrance Conductor
or Equivalent Area for
Parrell Conductorsa
(AWG/kcmil)
Size of Grounding
Electrode Conductor
(AWG/kcmil)
Copper Aluminum or
Copper-Clad
Aluminum
Copper Aluminum or
Copper-Clad
Aluminum
2 or smaller 1 or smaller 8 6
1 or 1/0 2/0 or 3/0 6 4
2/0 or 3/0 4/0 or 250 4 2
Over 3/0
through 350
Over 250
through 500

2

1/0
Over 350
through 600
Over 500
through 900
1/0 3/0
Over 600
through 1100
Over 900
through 1750
2/0 4/0
Over 1100 Over 1750 3/0 250
 Notes:
 1. Where multiple sets of service-entrance conductors are used as permitted
 in 230.40, Exception No.2, the equivalent size of the largest service-entrance
 conductor shall be determined by the largest sum of the areas of the
 corresponding conductors of each set.
 2. Where there are no service-entrance conductors, the grounding electrode
 conductor size shall be determined by the equivalent size of the largest
 service-entrance conductor required for the load to be served.
 aThis table also applies to the derived conductors of seperately derived
 ac systems.
 bSee installation restrictions in Section 250-64(A).


Back to Industry Tables Service Entrance Ground Calculator Disclaimer