Applications Suitable for use as follows:
- Branch-circuit wiring for general purpose, non-essential electrical systems in patient care areas of hospitals , medical, and
other types of health care facilities. Such areas include nursing homes, dental offices and outpatient facilities
- Use in hazardous anesthetizing areas and essential electrical system circuits are prohibited, except where permitted per
2005 NEC 517.30(C)(3)(3)
- Applications requiring redundant, decicated or isolated grounding paths
- Environmental air-handling spaces per NEC 300.22(C); Dry locations; fished or embedded in plaster
- Places of Assembly per NEC 518.4 and NEC 520.5
- Under raised floors for information technology equipment conductors
and cables per
NEC 645.5(D) & 645.5(D)(2)
- Multiple neutral and multi-circuit cables totaling more than 4 current-carrying conductors are now possible
|
Features
- Redundant ground paths for Patient Care Areas in Health Care Facilities
per NEC 517.13(a)&(b)
- Installation instructions provided with every reel and coil
- Simplified armored product application and installation
- Reduces installation costs up to 50% over pipe and wire
- Increase labor savings as compared to HCF Type AC Cable
- Cable reverse wound on reel for ease of pulling and installation.
When pulling from coils, pull from inside to ensure ease of installation
- Armored ground path is approximately 3.5 times better than HCF Type AC Cable and is equivalent
to a green insulated copper grounding conductor
- Easy to identify lightweight green armor
- UL Classified 1, 2, and 3 Hour Through-Penteration Firestop Systems:
W-J-3037, W-L-3110,W-L-3113, W-L-3117, W-L-3120,W-L-3121, W-L-3160, C-AJ-3115, C-AJ-3140, C-AJ-3142
C-AJ3145, C-AJ-3173, C-AJ-3202,C-AJ-4065,C-AJ-4046, F-C-3038
|